Equipment Co-location is a must have requirement for any medium to large business or service provider who requires maximum availability of systems and applications within a state of the art data centre facility.
Simtronic Technologies and it's wholesale partners operate a multihomed redundant network to all of our co-location racks which ensure your systems operate with a guaranteed network uptime of 99.95% or higher which provides your business with a high availability online presence while saving on the substancial costs of maintaining and implimenting your own network infastructure.

Simtronic Technologies operates it's network and provides co-location services within the Equinix Data Centre facility located at Mascot in Sydney. The Data Centre is one of the worlds leading network-neutral data centre facilities serving as a core hub for critical IP networks and Internet operations within Australia.
Our facility is strategically located close to the International Southern Cross Cable and around 8 kilometers from the Central Business District of Sydney providing you with unrivaled connectivity to Sydney and the world.
Facility Overview:
- Redundant power supplied by local utilities
- 6000KVA total facility power
- 10 amps at 240V/50Hz power per customer cabinet (Additional power avialable at cost)
- 750 watts power per square metre in technical areas
- -48 volts decentralized DC plant with BDFB distribution
- Dual, redundant/diverse A+B Power Distribution Units
- 2000KVA UPS System - Day 1, 3000KVA ultimate to N+1 configuration
- Dedicated clean earth system
- 4500KVA generator system under N+1 configuration - Day 1, 6750KVA ultimate. Fuel supply sufficient for 44 hours of operation under full load
|
- Overhead proprietary fibre guide system
- Overhead cable management system multi-tier ladder rack
- CAT 5e UTP, Fibre (MultiMode and Single Mode) and coaxual cable connections
- DSX-1 cross-connect system provides for T1, ISDN-PRI connectivity
- RJ-11, RJ-45, RJ-48, BNC and SC phyiscal interfaces standard
|
|
- Air-cooled chilled-water and cooling tower system designed to cool 750 watts per square metre for 22 degrees Celsius (71.6 degrees Fahrenheit) + 3 degrees.
- Humidity controlled to 50% + 20%
- N+1 per zone CRAC system
- Laser-based Very Early Smoke Detection Apparatus (VESDA)
- Double interlock preaction sprinkler system
|
- 24 x 7 x 365 security and CCTV surveillance (30 days of video recording)
- Biometric hand readers plus PIN code security
- Equinix issued photo IDs required for access to data centres
- Physical access control lists manage ingress and egress
|
|